Summary
ZW27B-12 type outdoor HV AC vacuum circuit breaker is used to make and break load current, overload current and short-circuit
current in the power system with rated voltage 12kV, three-phase AC 50/60Hz. It is applicable to substations, industrial and minding
enterprises, unban and rural electric power networks, especially to the occasions with frequent operation and automatic power
distribution networks for power network control and equipment protection. It can be also used as a sectionalizing switch after equipped
with a disconnect switch, thus the installation space and working hours can be saved more. The product conforms to the standards of
IEC62271-100 & GB1984: AC high voltage circuit breaker, IEC60694 & GB/T11022: HV general technical requirement of switch and
control apparatus.
Ambient conditions
1. Altitude: ≤1500m;
2. Ambient temperature: -40℃~+45℃;diurnal temperature rang ≤25℃;
3. Wind speed: ≤34m/s (wind pressure ≤700Pa);
4. Earthquake intensity: ≤grade 8;
5. Relative humidity: monthly average ≤90%; daily average ≤95%. Dew may be condensed in the interior of the tank body when high
humidity drop rapidly;
6. Ice thickness: ≤10mm;
7. Pollution degree: ≤Ⅳ(GB5582);
8. Applicable occasions: no fire and explosion danger, no chemical corrosion and no frequent severe vibration;
9. Neutral grounding mode: neutral non grounding, neutral grounding via arc-extinguishing coil, neutral grounding via low-resistance.
Model
Technical specification
No.
|
Item
|
Unit
|
Data
|
1
|
Rated voltage
|
kV
|
12
|
2
|
Rated current
|
A
|
630
|
3
|
Rated insulation level
|
1min P.F
withstand voltage
|
Dry test
|
kV
|
42
|
Wet test (to earth, external insulation)
|
34
|
Lightning impulse withstand voltage(peak)
|
75
|
4
|
Rated frequency
|
Hz
|
50/60
|
5
|
Rated short-circuit breaking current
|
kA
|
20
|
6
|
Rated operating sequence
|
|
O-0.3s-CO-180s-CO
|
7
|
Breaking times of rated short-circuit breaking current
|
times
|
30
|
8
|
Rated short-circuit making current(peak)
|
kA
|
50
|
9
|
Rated peak withstand current
|
50
|
10
|
Rated short-time withstand current
|
20
|
11
|
Rated short-circuit duration
|
s
|
4
|
12
|
Rated operating voltage /rated auxiliary loop voltage
|
V
|
AC/DC 220
|
13
|
Average opening speed
|
m/s
|
1.0±0.3
|
14
|
Average closing speed
|
1.0±0.25
|
15
|
Contact close-bouncing time
|
ms
|
≤2
|
16
|
Three-phase opening/closing non-simultaneity
|
≤2
|
17
|
Closing time
|
ms
|
25~50
|
18
|
Opening time
|
At highest rated operating voltage
|
15~50
|
At lowest rated operating voltage
|
30~16
|
19
|
DC resistance for each phase loop
|
μΩ
|
≤120(200 with isolator)
|
20
|
Phase-to-phase spacing(measure from arc chamber’s end)
|
mm
|
260±2.0
|
21
|
Mechanical life
|
times
|
10000
|
22
|
Net weight
|
kg
|
135(155 with isolator)
|
|
Main function features
1. The product can be equipped integratedly with a built-in voltage transformer to simplify the construction and installation;
2. The switch can be equipped with an external isolator according to the users’ request. The structure can be compact.
3. The operating mechanism may be equipped with an anti-trip device and counter which is convenient for the users to accurately know
the operating life of the product;
4. Iron or stainless steel body, manual or electric mechanism is available for free chioce;
5. The product can be equipped with metering tank to realize electricity consumption monitoring.
6. The operating mechanism can be permanent magnet type arrcording to the users’ request;
7. The switch can be equipped with a built-in zero sequence CT, the reserved automation interface is convenient for the users to upgrade
the line.
Outline and installation dimension